Required applicant information
The following applicant information is required:
- Name of applicant
- Business address
- VBA licence number
- Contact details, and
- The installation address
Gas installation or Type B appliance information
Details about the complex gas installation or Type B appliance must also be provided.
The information required is dependent on a number of factors detailed in Schedules 7, 8, 9, 10 and 11, located at the end of the Regulations.
Thresholds have been set to categorise gas installations – the information required depends on the category of the gas installation.
Applications for all complex gas installations must include the information listed in Schedule 7 of the Regulations.
However, Regulation 26 (2) states that an application must contain or be accompanied by the information listed in Schedule 8, in addition to the Schedule 7 requirements if the gas installation is to:
- have a total gas rate exceeding 3.8 gigajoules (3800 MJ) per hour, or
- have an operating pressure exceeding 200 kilopascals, or
- be installed in a building exceeding 10 storeys above the ground.
If a gas installation contains a Type B appliance, an application for acceptance of the gas installation must also contain or be accompanied by the information listed in Schedule 9.